Thursday, April 16, 2015

16/04/2015



-          Boiler Feed water flow tuning improved
-          11:03 Synchronisation and load up 356 MW. Boiler  and feed water flow tuning.
-          14:10 Unit trip due to Boiler main steam temperature drop (Turbine protection): Boiler load control problem.
-          18:00 Synchronisation: load steady (around 200 MW) over night.

Wednesday, April 15, 2015

15/04/2015




Between 13/04/2014 to 15/04/2014

-          Unit 6 restart on by-pass operation.
-          Feed water flow tuning. This is the biggest interface problem (P02/P03/P17). PAC and Belfort still struggling to find the right settings to tune this loop. Most of the boiler trips are due to this function.
-          Boiler economizer soot blowing (Hitachi). The boiler tube have never been cleaned before: This may explain this difficulty to tune the boiler feed water flow.

Tuesday, April 14, 2015

14/04/2015

Unit on By-Pass Operation

Monday, April 13, 2015

13/04/2015

Re-Start of Unit on By-Pass Operation