Saturday, February 28, 2015

28/02/2015



-          Removing short-circuit bar complete
-          5h00 Back energized (Problems with 400 kV line – ESKOM)
-          Turbine @ 3000 RPM expected 9h30

Thursday, February 26, 2015

27/02/2015


-          Electrical test was stopped 23h00 yesterday due to several boiler trips (HP by-pass)
-          6h30 Turbine @ 3000 RPM
-          Electrical tests ongoing
-        12:00 Short circuit test complete
-          Removing short-circuit bar by ESKOM ongoing
-          Open circuit tests forecast : 18h00

26/02/2015


Turbine at 3000 RPM forecasted tonight 18h00!
  2h45 CT replacement complete
3h00 Aux boiler started
-          8h00 boiler filling
-          10h00 Boiler must be drained due to high conductivity
-          15h00 Boiler start
16h00 : boiler 20 burners on
           : steam water cycle in by-pass operation (waiting for water and steam quality)
17h50 Turbine start
-          18h00 Turbine @ 3000 RPM – ready for electrical test
 20h00: Boiler trip; HP by-pass issue.

Several attempts to restart the boiler were performed unsuccessfully.

23h00: Hitachi investigating..



Tuesday, February 24, 2015

25-02-2015

Shut-Down to replace faulty Generator CT
from 25/02/2015 to 26/02/2015

CT Replaced on 25/02/2015 @24:00

Boiler Re-Start @ 3:00

2015/02/24



-         6h00 Excitation panel repaired and ready
-         7h45 Turbine @ 3000 RPM
-         8h00 Start of electrical test – Excitation 20%

-         14h00 One CT on neutral point is unbalanced and protection relays are tripping
-         15h00 Excitation test on short-circuit complete (Excitation up to 80%)
-         18h30 CT issue still under investigation

Monday, February 23, 2015

2015/02/23


06:00 - ST on Baring
ST Turning on Steam
06:07 - STG @3000RPM
  6h30 Start of electrical test
06:56 - Boiler Tripped on Boiler Protection - FO Lost
Expected restart 12h00
11:53 - Mill 20 in service
 12h00 Boiler started, system in by-pass operation
12:20 - ST Turn on Steam
12h25 Turbine @ 3000 RPM
12h30 Ready for electrical test (Excitation)
14h00 Excitation panel test (10% load)  
15h00 Excitation panel trip (one relay burned) - Burned relay will be replaced by Unit 5 relay

17:26 - Steam turbine OVERSPEED TEST and Tripped on 3300RPM


 18:34 - ST on Turning Gear
01:00 - Boiler Fires In
02:45 - Attempt to bring Mill30 in - Failed
03:45 - Fires Out - Loss of Aux boilers
05:05 - Fires In
05:25 - By-Pass Operation