Thursday, March 12, 2015

12/03/2015

FORECAST PROGRAMME


ACTUAL @7:00
11/03/2015@22:52 Turbine trip due to high exhaust temperature HP
-          GCB didn’t open, and we get low reverse power (reverse power was not detected by gen protection device)
-          The case is under investigation


ACTUAL @18:00
-          Reverse power issue resolved by setting changes in the gen. protection relay
-          17:00 Synchronization
-          Reverse power test successful
-          17:20 Synchronization
-          Power increase to 150MW

LOAD PROFILE FROM DCS 


No comments: